Ceiling stains at bath fans: don’t call a roofer

As home inspectors, we often find stained ceilings around bathroom exhaust fans. We also find a lot of stains in the attic where the bathroom exhaust fan terminates at the roof.

Ceiling-Stain-bath-fan

While the knee-jerk reaction for most homeowners is to call a roofer when a stain shows up on their ceiling, this type of staining is rarely the result of a roof leak. This is typically the result of condensation.

The job of a bathroom exhaust fan is to remove moist air and foul odors from the bathroom. When moist air is carried through a duct that passes through a cold attic space, you’ll get condensation inside the duct. When enough condensate accumulates, it drains to the bottom, leaks through the fan, and stains the ceiling. It’s as simple as that. To help prevent these stains from occurring, take these steps to minimize condensation inside the duct.

Use an insulated duct inside the attic

This is a no-brainer. If you don’t have an insulated duct in your attic, don’t try to wrap a bunch of fiberglass insulation around it in a feeble attempt to insulate. That’s a time-consuming chore that probably won’t do anything. Instead, replace the uninsulated duct with an insulated one. They’re not expensive, and it’s a lot less work than trying to insulate an existing duct. Here’s an example of one sold on Amazon:

Flex duct Insulated

Also, don’t use metal ductwork. It’s a good conductor of cold, and it has too much thermal mass, which means you’ll have excessive condensation inside the duct.

Use the shortest run possible

The longer the bath fan duct, the greater the potential for condensation inside the duct. These ducts will sometimes run from one side of the attic to the other to create a more aesthetically appealing roof line, but this increases the potential for condensation and reduces the performance of the fan.

Ensure the duct is tightly connected to a roof cap with a damper

The damper will help prevent cold air from dumping back into the house, which may lead to condensation at the fan. The duct should not be aimed at a roof vent or have any loose connections inside the attic.

Anything other than a tight connection to a dampered roof cap is an improper installation that can lead to problems.

If you recently had your roof covering replaced, have someone get up into the attic to verify the bath fan duct is still tightly connected. It’s common for roofing nails to knock the bath fan duct right off the roof, or at least knock it loose.  Click the photo below to see a large image showing exactly how this happens.

Loose-bath-fan-duct-in-attic

Here’s a photo of a loose duct at a new construction inspection.

Loose bath fan duct new construction

When the fan connection is loose, moist air can escape into the attic, and cold air from the attic will dump down the duct when the fan isn’t running, increasing the potential for condensation in the duct.

Check the damper at the roof cap periodically

This should be a part of any home maintenance inspection, whether the homeowner or a home inspector does the inspection.

If the damper at the roof cap gets stuck shut, moisture will condense inside the duct. To check the operation of the damper, turn the fan on and ensure air is coming out of the terminal. If there’s no air movement, check to make sure the damper opens freely. Dampers made before 2006 had a serious flaw that caused the damper to get stuck closed all by itself. For more information on that topic, click here: A Common Problem with Roof Caps for Bath Fans.

The other common reason for roof caps to get stuck shut is wasps.  They love to make nests inside of roof caps, and even the smallest nests are enough to prevent a roof cap from opening. Just one more reason to hate wasps, right?

Small wasp nest at roof cap

If it’s not safe to walk the roof, try looking up at the roof cap from the ground with a pair of binoculars while someone inside the house turns the bath fan on and off; if it’s working properly, you should be able to see the damper opening and closing. If it doesn’t open and close, you need to get to the bottom of it.

6 responses to “Ceiling stains at bath fans: don’t call a roofer”

  1. Reuben
    July 25, 2014, 2:25 pm

    Testing capcha

  2. Mark Brandon
    July 30, 2014, 9:54 am

    Great Blog Reuben!

    This is one of the blogs I do love! Very informative.. This also serves a way for people who doesn’t have any idea about bath fan inspections..

    🙂

  3. Mark Erickson
    July 31, 2014, 10:11 am

    Forgot to come back and post my comment. On the “Common Problem” post, the link to the installation instructions is dead. New link is http://www.broan.com/common/productDigitalAssethandler.ashx?id=923c5d0c-876e-4cb7-b2fd-8e4e40faf891

    Thanks for this great blog, Reuben.

  4. Reuben Saltzman
    July 31, 2014, 2:07 pm

    @Mark – fixed. Thank you!

  5. Mirela Avram
    April 18, 2025, 1:11 am

    Great tips on preventing bathroom fan duct stains! Just wondering, is it really better to replace metal ducts entirely instead of trying to insulate them? Seems like a bigger job. Also, how often should we check the damper to avoid issues? Thanks!

  6. Reuben Saltzman
    April 18, 2025, 11:46 am

    Hi Mirela,

    If you don’t have a condensation problem, it’s not worth replacing a metal duct. As as for checking the damper, do it annually.